Analisis Efisiensi Kinerja Heat Exchanger Tipe Shell and Tube Berdasarkan Parameter Laju Alir dan Fouling Factor

Salwa Malani, Cintiya Septa Hasannah

Abstract


The purpose of this study is to determine the results of the evaluation of shell and tube type heat exchanger performance efficiency based on flow rate parameters and fouling factors. In the evaluation of Heat Exchanger (HE-105) performance, two types of data collection were carried out, namely primary data collection used for basic analysis of Heat Exchanger (HE-105) performance evaluation at refinery facilities at PT X and secondary data collection was carried out as a calculation step in the evaluation of Heat Exchanger (HE-105) performance. The results showed that the actual average Rd (fouling factor) value of 0.0012 kcal/m2 hr C is which greater than the design Rd, this is due to the accumulated fouling. The average value of efficiency in the design is 98.41%, and the actual efficiency is 86.29%. The actual average efficiency value is smaller than the design average efficiency value, this is due to the influence of the high flow rate which causes the contact time between temperatures to decrease. However, the average efficiency value is still relatively high, indicating that the Heat Exchanger (HE-105) is still very feasible to use.


Keywords


heat exchanger, flow rate parameter, fouling factor

Full Text:

PDF

References


Flynn, A. M., Akashige, T., & Theodore, L. 2019. Kern’s Process Heat Transfer Second Edition.

Kern, D. Q. 1965. Process Heat Transfer.

Li, W., & Hrnjak, P. 2021. Single-phase flow distribution in plate heat exchangers: Experiments and models. International Journal of Refrigeration, 126, 45–56.

Nur’ain Hanna Eryati, & Hidayati Nur. 2021. Evaluasi Kinerja Hot Main Column Bottooms Raw Oil Exchanger (15-E-101) Pada Unit Recidu Catalytic Cracing (RCC).

Putra, I. 2017. Studi Perhitungan Heat Exchanger Type Shell and Tube Dehumidifier Biogas Limbah Sawit Untuk Pembangkit Listrik Tenaga Biogas. Jurnal Polimesin, 15(2), 1693–5462.

Robiyanyusra, Gani Usman A, & Taufiqurrahman Muhammad. 2021. Analisis Efektivitas Laju Perpindahan Panas Alat Penukar Kalor Tipe Double Pipe. Jurnal Teknologi Rekayasa Teknik Mesin (JTRAIN), 2(2), 97–104.

Sari, H. N., Made Arsana, I., & Hidayatulloh, M. 2022. Pengaruh Fouling Factor Terhadap Performa Heat Exchanger Tipe Shell and Tube. Jurnal Mekanova, 8(1), 55–1.

Sebayang, M. 2019. Evaluasi Kinerja Heat Exchanger dengan Metode Fouling Faktor di Laboratorium Satuan Operasi PTKI Medan.

Tumbade F Gresta, Sappu Frans P, & Lumintang Romels A. C. 2022. Revitalisasi Alat Penukar Kalor Tipe Shell and Tube. In Jurnal Poros Teknik Mesin Unsrat, 11(1).

Wahyudi, A. T., Leestiana, F., & widodo, R. 2022. Evaluasi kinerja Heat Exchanger pada Fasilitas Kilang PPSDM Migas dengan Metode Perhitungan Fouling Factor. Majalah Ilmiah Swara Patra, 12(1).




DOI: http://dx.doi.org/10.33087/jiubj.v24i2.4718

Refbacks

  • There are currently no refbacks.


Creative Commons License
This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.

ADRESS JOURNAL

JURNAL ILMIAH UNIVERSITAS BATANGHARI JAMBI (JIUBJ)
Published by Lembaga Penelitian dan Pengabdian kepada Masyarakat
Adress: Jl.Slamet Ryadi, Broni-Jambi, Kec.Telanaipura, Kodepos: 36122, email: jiubj.unbari@gmail.com, Phone: 0741-670700

Creative Commons License This work is licensed under a Creative Commons Attribution-ShareAlike 4.0 International License.